| Öğe açıklaması | Shunt release (2) 220-240 VAC/DC / accessories, 2ND shunt release, only in combination with a "first" shunt release., cannot be combined with an undervoltage release., maximum operating frequency actuations/minute 3, limited to 3/MIN due to the high pick-up current for 35 MS., please note - the circuit-breaker's switching frequency = 60/H, rated control voltage US 208 - 240 V AC 50/60 HZ, 208 - 250 V DC v, operating range x US 0, 7 - 1, 1 factor, max. holding current in 0.034 A, max. continuous power AC/DC 9 VA/W, circuit-breaker total switching time US=100% 30 (IZMX16..., INX16...), 35 (IZMX40..., INX40...) MS, for use with IZMX16..., IZMX40..., INX16..., INX40 |