| Öğe açıklaması | Shunt release 60 VDC / accessories, shunt release (for power circuit breaker), CAN be combined with an undervoltage release or a second shunt release., maximum operating frequency actuations/minute 3, limited to 3/MIN due to the high pick-up current for 35 MS., please note - the circuit-breaker's switching frequency = 60/H, rated control voltage US 60 V DC v, operating range x US 0, 7 - 1, 1 factor, max. holding current in 0.07 A, max. pick-up current (35MS) in 7.84 A, max. continuous power AC/DC 5 VA/W, max. pull-in power (35MS) AC/DC 540 VA/W, circuit-breaker total switching time US=100% 30 (IZMX16..., INX16...), 35 (IZMX40..., INX40...) MS, for use with IZMX16..., IZMX40..., INX16..., INX40 |