| Artikelbeschreibung | Safety barrier (zener barrier), installation in zone 2, 2 channels, max. voltage uo: 13, 7 V, max. current IO: 14, 5 MA, max. power po: 50 MW, max. permissible external capacity CO for iib: 5 µf, max. permissible external capacity CO for iic: 0, 79 µf, max. permissible external inductance lo for iib: 560 MH, max. permissible external inductance lo for iic: 160 MH, power supply: Regulated, 10 V DC, maximum output current: 10 MA, potential: Channel 1 positiv, channel 2 positiv, especially suitable for: Strain gauge for signal/sense |